| Date: 9/10/2008 | Time: | Report ID: |
| Property: 55 Sample AVE E Puyallup, WA 98374 |
Customer: John Doe |
Real Estate Professional: |
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the inspector should be considered before purchasing this home. Any recommendations by the inspector to repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs associated with further inspection fees and repair or replacement of item, component or unit should be considered before you purchase the property.
Inspected (IN) = I visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not in this home or building.
Repair or Replace (RR) = The item, component or unit is not functioning as intended, or needs further inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition may not need replacement.
In Attendance: Customer and their agent | Type of building: Single Family (2 story) | Approximate age of building: Over 25 Years |
Temperature: Below 65 | Weather: Clear | Ground/Soil surface condition: Dry |
Rain in last 3 days: No |
| Styles & Materials Roof Covering: 3-Tab fiberglass Viewed roof covering from: Walked roof Sky Light(s): Four Chimney (exterior):
Block |
||||||||||||||||||||||||||||||||||||
1.3 Roofing on North side of home does not have a drainage
system. Recommend installation by a qualified contractor.![]() |
| Styles & Materials Siding Style: Lap T-111 Siding Material: Wood Exterior Entry Doors: Wood Appurtenance:
Deck with steps |
||||||||||||||||||||||||||||||||||||||||||||||||||||||
2.0 (1) Failed caulk around entry door and holes in siding near
window at rear of home. Recommend re-caulk to prevent
possible water intrusion.![]() | ![]() |
(2) Siding on south side of the home has evidence of water
retention. Recommend further evaluation by a qualified
contractor.![]() |
(3) Fence support is in contact with siding. This is considered a
conducive condition for wood destroying organisms.
Recommend repair by a qualified contractor.![]() |
(4) Siding on North side of home is deteriorated. Recommend
replace/repair by a qualified contractor.![]() |
(5) Fascia board ends are severely deteriorated and wood rot is
present. Recommend repair/replace by a qualified contractor.![]() | ![]() |
2.3 (1) Top deck step is missing tread board. This is a trip hazard.
Recommend installation.![]() |
(2) Middle post on front deck is in contact with soil.
Recommend adequate clearance from wood to soil to prevent
rot.![]() |
(3) Multiple support members on front deck have wood rot.
Recommend replacement by a qualified contractor.![]() | ![]() |
(4) Bottom side of decking at rear deck shows evidence of water
retention. This may lead to wood rot and failure.
Recommend repair/replace by a qualified contractor.![]() |
(5) Front and rear decks are missing proper railing. This is a
safety hazard. Recommend spindles be no larger than 4
inches in width. Recommend installation by a qualified
person.![]() |
2.4 Vegetation in contact with the home is considered a
conducive condition for wood destroying organisms.
Recommend trimming vegetation to provide adequate
clearance.![]() |
2.6 Recommend removal of all cellulose debris near the
foundation. ![]() | ![]() |
| Styles & Materials Ceiling Materials: Drywall Wall Material: Drywall Floor Covering(s): Carpet Vinyl Interior Doors: Hollow core Window Types: Sliders Cabinetry: Wood Countertop:
Laminate |
||||||||||||||||||||||||||||||||||||||||||||||||||||||
4.2 Caulk is failing at tub and toilet in upper bathroom and at
toilet in lower bathroom. Recommend re-caulk to prevent
possible water intrusion.![]() | ![]() |
![]() |
![]() |
(2) Entry door is missing dead bolt. Recommend installation.![]() |
(3) Door knob at back door is broken. Recommend
repair/replace by a qualified person.![]() |
| Styles & Materials Foundation: Masonry block Poured concrete Method used to observe Crawlspace: No crawlspace Floor Structure: Slab Wall Structure: Wood Ceiling Structure: 2X4 Roof-Type: Gable Method used to observe attic: From entry Attic info:
Attic access |
||||||||||||||||||||||||||||||||||||||||||
| Styles & Materials Water Source: Public Washer Drain Size: 2" Diameter Water Heater Power Source: Electric Water Heater Capacity:
50 Gallon (2-3 people) |
||||||||||||||||||||||||||||||||||||
6.0 (1) Both bathroom sinks are missing plungers. Recommend
installation by a qualified person.![]() |
(2) Recommend the dishwasher drain line have a loop to prevent
back flow of water.![]() |
6.1 Hose bib at rear of home leaks. Recommend repair/replace
by a qualified person.![]() |
| Styles & Materials Electrical Service Conductors: Overhead service Panel Type: Circuit breakers Electric Panel Manufacturer: FEDERAL PACIFIC Wiring Methods:
Not Visible |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
7.0 A Federal Pacific Electric (FPE) "Stab-Lok" service panel
was present. FPE circuit breakers may fail to trip in
response to an over current or a short circuit. A circuit
breaker that may not trip does not afford the protection
that is intended and required, creating a fire hazard.
Simply replacing the circuit breakers might not be a
reliable repair. It is the electric components or appliances
that typically cause problems, e.g., a short in an
appliance, an electric outlet, or a light switch. Electric
panels and circuit breakers are designed to prevent
personal injury and property damage in the event of a
short (or other problem) by shutting down the electric
current to the faulty appliances or electrical components.
There appears to be no official recall on these panels,
mainly because the companies that made these panels
are out of business. Due to the problems associated with
Federal Pacific Electric panels and inadequate clearance
between breakers and edges of covers (removing covers
can dislodge circuit breakers and/or all circuits might
need to be shut off), I do not remove covers; type of power
cable and/or main wiring was unknown; type of branch
wiring was unknown; adequacy of grounding system was
unknown; and condition of wiring and any specific wiring
problems was unknown. For additional helpful information
about Federal Pacific electric panels, www.inspect-ny.com/fpe/fpepanel.htm
www.inspect-ny.com/fpe/fpe.html
www.inspect-ny.com/fpe/fpecpsc.htm
www.inspect-ny.com/fpe/fpetest.htm
This electric panel might be at the end of its useful life. Standards generally recognize the life expectancy of electric panels to be about 25 years. With older panels, contact points become corroded, possibly causing arcing, brownouts, and, at worst case, fires, personal injury, and property damage. I do not remove any circuit breakers to inspect for corrosion at the circuit breaker contact points since that would require shutting off electric service to remove the circuit breakers. There is the possibility that this electric panel has been upgraded, but only a licensed electrician can make that determination since electric service might again have to be shut off and circuit breakers removed. Note that home inspectors are not licensed as electricians in the State of Washington. Recommend further evaluation by a licensed electrician before close of escrow.
![]() |
7.3 (1) Multiple receptacles and switches are missing wall plates.
This is a safety hazard. Recommend installation.![]() | ![]() |
(2) Light fixture in lower bathroom is inoperable. Recommend
light bulb replacement and further evaluation by a qualified
electrician if needed.![]() |
(3) Light bulb missing in fixture at doorway in basement. Unable
to verify operation. Recommend installation of light bulb to
verify operation.
7.4 Receptacles in two lower bedrooms are not grounded.
Recommend repair by a qualified electrician.![]() |
7.7 Smoke alarm missing in upper hallway and all bedrooms.
Smoke alarm in basement needs battery replacement.
Recommend all rooms have smoke alarms installed to
conform with current safety standards.![]() |
| Styles & Materials Heat Type: Forced Air Electric heat Energy Source: Electric Number of Heat Systems (excluding wood): Two Filter Type: Disposable Filter Size: 16x20 Types of Fireplaces: Solid Fuel Operable Fireplaces: Two Number of Woodstoves:
Two |
||||||||||||||||||||||||||||||||||||||||||||||||
| Styles & Materials Attic Insulation: Blown Ventilation: Gable vents Ridge vents Soffit Vents Exhaust Fans: Fan only Dryer Power Source: 220 Electric Dryer Vent:
Metal |
||||||||||||||||||||||||||||||||||||
9.2 Dryer vent does not have a screen. Recommend installation
to prevent pest intrusion.![]() |
| |||||||||||||||||||||||||||||||||||||
10.0 Recommend dishwasher have a support bracket installed to
prevent tipping.![]() |
10.1 Recommend range have support bracket installed to prevent
tipping.![]() |
| |||||||||||||||||||||||||||||||||||||||||||||||||
11.3 Evidence of conditions conducive to wood destroying
organisms were detected. Such infestations may be
eliminated by removal of all infested wood and correction of
any contributing conducive conditions. The services of a
licensed, qualified contractor should be obtained.
WSDA License #76560
213 Nelsen St NE
Orting, WA 98360
253-508-0621
Customer
John Doe
Address
55 Sample AVE E
Puyallup, WA 98374
| 1. Roofing | |||||||
|
| 2. Exterior | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
| 4. Interiors | |||||||||||||||||||
|
| 6. Plumbing System | |||||||||||||||||
|
| 7. Electrical System | ||||||||||||||||||||||||||||||||||
|
| 9. Insulation and Ventilation | |||||||
|
| 10. Built-In Kitchen Appliances | ||||||||||||||
|
| 11. Complete Wood Destroying Organisms Inspection Report | ||||||
|
|
INVOICE |
| Cascade Home Inspections
WSDA License #76560 213 Nelsen St NE Orting, WA 98360 253-508-0621 Inspected By: Kevin Pierce |
Inspection Date: 9/10/2008
Report ID: |
| Customer Info: | Inspection Property: |
| John Doe
123 Sample Road Tacoma wa 98445 Customer's Real Estate Professional: |
55 Sample AVE E Puyallup, WA 98374 |
| ||||
Tax $0.00 | ||||
| Total Price $0.00 |
Payment Method: Check
Payment Status: Paid
Note:
![]() Cascade Home Inspections
WSDA License #76560 |
This inspection was performed in accordance with and under the terms of a Pre-Inspection Agreement. The agreement was signed and agreed upon before the preparation of this report and a signed copy of the agreement is available upon request. An unsigned copy of the agreement may be attached to this report for your information or it may also be available on the home inspection company web site.